NUT Configuration (UPS Graceful Shutdown)

Network UPS Tools configuration for graceful shutdown on power loss.

Overview

[Forza NT-1012U UPS]
        │ USB
      [NAS]
   NUT Server
        │ Network
┌───────┴───────┐
│               │
▼               ▼
[Mini PC]    [RPi 4]
NUT Client   NUT Client

Topology

  • NAS connects to UPS via USB (master)
  • Mini PC and RPi 4 are network clients
  • All devices gracefully shutdown when battery is low

NAS Configuration (NUT Server)

Install NUT

sudo apt install nut nut-server nut-client

Identify UPS

# List connected UPS devices
sudo nut-scanner -U

# Expected output (Forza usually appears as blazer_usb or nutdrv_qx)
[nutdev1]
    driver = "blazer_usb"
    port = "auto"

Configure UPS Driver (/etc/nut/ups.conf)

[forza]
    driver = blazer_usb
    port = auto
    desc = "Forza NT-1012U 1000VA"
    vendorid = 0001
    productid = 0000
    default.battery.voltage.high = 26.0
    default.battery.voltage.low = 20.8

Note: If blazer_usb doesn't work, try nutdrv_qx driver.

Configure NUT Mode (/etc/nut/nut.conf)

MODE=netserver

Configure Network Access (/etc/nut/upsd.conf)

LISTEN 0.0.0.0 3493
LISTEN :: 3493

Configure Users (/etc/nut/upsd.users)

[admin]
    password = your-secure-password
    actions = SET
    instcmds = ALL

[upsmon]
    password = monitor-password
    upsmon master

[upsmon_slave]
    password = slave-password
    upsmon slave

Configure UPS Monitor (/etc/nut/upsmon.conf)

MONITOR forza@localhost 1 upsmon monitor-password master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower

# Notifications
NOTIFYCMD /usr/sbin/upssched
NOTIFYFLAG ONLINE     SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT     SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT    SYSLOG+WALL+EXEC
NOTIFYFLAG FSD        SYSLOG+WALL+EXEC
NOTIFYFLAG SHUTDOWN   SYSLOG+WALL+EXEC

Start Services

sudo systemctl enable nut-server nut-client
sudo systemctl start nut-server nut-client

# Verify
upsc forza@localhost

Mini PC Configuration (NUT Client)

Install NUT Client

# On Proxmox host
apt install nut-client

Configure NUT Mode (/etc/nut/nut.conf)

MODE=netclient

Configure UPS Monitor (/etc/nut/upsmon.conf)

MONITOR forza@192.168.0.12 1 upsmon_slave slave-password slave
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POLLFREQ 5
POLLFREQALERT 5
DEADTIME 25

NOTIFYFLAG ONLINE     SYSLOG+WALL
NOTIFYFLAG ONBATT     SYSLOG+WALL
NOTIFYFLAG LOWBATT    SYSLOG+WALL
NOTIFYFLAG FSD        SYSLOG+WALL
NOTIFYFLAG SHUTDOWN   SYSLOG+WALL

Start Service

systemctl enable nut-client
systemctl start nut-client

# Verify connection
upsc forza@192.168.0.12

RPi 4 Configuration (NUT Client)

Start9 uses a custom OS, so NUT configuration may differ.

Option 1: SSH-based Shutdown

If Start9 doesn't support NUT natively, configure NAS to SSH shutdown:

Add to NAS /etc/nut/upssched.conf:

CMDSCRIPT /usr/local/bin/nut-notify.sh
AT LOWBATT * START-TIMER shutdown-rpi4 30

Create /usr/local/bin/nut-notify.sh:

#!/bin/bash
case $NOTIFYTYPE in
    LOWBATT)
        # Shutdown Start9 via SSH
        ssh root@192.168.0.11 "shutdown -h now"
        ;;
esac

Option 2: Standard NUT (if Start9 supports)

Same as Mini PC configuration, pointing to NAS.


Shutdown Sequence

When power fails:

  1. ONBATT - UPS switches to battery
  2. Log event, send notification

  3. LOWBATT - Battery reaches threshold (~20%)

  4. Start shutdown timer (60 seconds)
  5. Notify all clients

  6. FSD (Forced Shutdown) - Master initiates shutdown

  7. Clients receive FSD and begin shutdown
  8. Order: RPi 4 → Mini PC → NAS (master last)

  9. POWEROFF - NAS sends UPS kill command

  10. UPS powers off after delay

Notification Script

Create /usr/local/bin/nut-notify.sh on NAS:

#!/bin/bash
# NUT notification script

NTFY_URL="https://notify.cronova.dev/cronova-critical"

case $NOTIFYTYPE in
    ONLINE)
        MSG="UPS is back on line power"
        ;;
    ONBATT)
        MSG="UPS is on battery - check power"
        ;;
    LOWBATT)
        MSG="UPS battery is LOW - shutdown imminent"
        ;;
    FSD)
        MSG="UPS forced shutdown in progress"
        ;;
    SHUTDOWN)
        MSG="System is shutting down"
        ;;
    *)
        MSG="UPS event: $NOTIFYTYPE"
        ;;
esac

# Send to ntfy
curl -d "$MSG" "$NTFY_URL" 2>/dev/null

# Log
logger -t nut-notify "$MSG"

Make executable:

chmod +x /usr/local/bin/nut-notify.sh

Testing

Test UPS Communication

# On NAS
upsc forza@localhost

# Expected output:
# battery.charge: 100
# battery.voltage: 26.00
# device.type: ups
# input.voltage: 220.0
# output.voltage: 220.0
# ups.load: 15
# ups.status: OL

Test Client Connection

# On Mini PC
upsc forza@192.168.0.12

Simulate Power Failure (CAREFUL!)

# On NAS - Force shutdown test
sudo upsmon -c fsd

# This will initiate shutdown sequence!
# Only test when prepared for actual shutdown

Test Notifications

# Manually trigger notification
NOTIFYTYPE=ONBATT /usr/local/bin/nut-notify.sh

Monitoring

Add to Uptime Kuma

  • TCP Check: 192.168.0.12:3493 (NUT server)
  • Alert: If NUT server is down, UPS monitoring is offline

Prometheus Metrics (Optional)

Use nut_exporter:

docker run -d --name nut-exporter \
  -e NUT_EXPORTER_SERVER=192.168.0.12 \
  -p 9199:9199 \
  druggeri/nut_exporter

Troubleshooting

UPS Not Detected

# Check USB
lsusb | grep -i ups

# Check driver
sudo upsdrvctl start

# Try different drivers
# Edit /etc/nut/ups.conf and try: nutdrv_qx, blazer_usb, usbhid-ups

Permission Issues

# Add nut user to dialout group
sudo usermod -aG dialout nut

# Check USB permissions
ls -la /dev/bus/usb/*/*

Client Can't Connect

# Check firewall
sudo ufw allow 3493/tcp

# Check NUT is listening
ss -tlnp | grep 3493

# Check upsd.conf LISTEN directive

Reference


Forza NT-1012U Specs

Spec Value

| Capacity | 1000VA / 500W | | Input Voltage | 220V | | Battery | 12V 7Ah x2 | | Runtime (180W load) | ~15-20 min | | Interface | USB | | Driver | blazer_usb or nutdrv_qx |